This report presents the results of continuous emission monitoring from BLCP Power Station stacks for January 2017, covering data from Unit 1 and Unit 2 throughout the month.

For Sulfur Dioxide (SO2), emission levels for both Unit 1 and Unit 2 were found to be consistently below the Thai legal standard of 320 ppmvd@7%O2 and the EIA report standard of 262 ppmvd@7%O2 throughout January 2017.

Regarding Nitrogen Oxides (NOx), monitoring results showed that emission levels for both units remained below the Thai legal standard of 350 ppmvd@7%O2 and the EIA report standard of 241 ppmvd@7%O2 throughout the period.

Opacity measurements of emissions released into the atmosphere for both Unit 1 and Unit 2 also consistently showed low levels throughout January 2017, with most readings below 20%.

Overall, the results of air pollutant emission monitoring from BLCP Power Station stacks in January 2017, including Sulfur Dioxide, Nitrogen Oxides, and Opacity, were all within the specified criteria and below the relevant standards.

Full details and graphical data are available in the attached file.